| LME.Copper | 14157.00 |
| LME.Aluminium | 3266.00 |
| Currency | Value | Edit | |
| USD CB RF | 85.1645 | 0.1509 | |
| EUR CB RF | 98.7312 | 0.3960 |
1. Electric conductor – twisted from copper wires (grade 5).
2. Semi-conductive shields from electric conductive rubber REM-1.
3. Insulation of main conductors from rubber RTI-1 based on natural and butadiene rubber.
4. Ground conductor.
5. Additional conductor with rubber insulation RTI-1 based on natural and butadiene rubber.
6. Inner sheath based on isoprene and butadiene rubber.
7. Outer sheath from flame-retardant, oil-resistant rubber RSHN-1.
|
Number and cross section of veins |
Nominal outer diameter of the cable |
Estimated cable weight, kg/km |
||
|
basic |
grounding |
supportive |
||
|
3 х 10 |
1 х 6 |
– |
40,4 |
1795 |
|
3 х 16 |
1 х 6 |
– |
43,0 |
2139 |
|
3 х 25 |
1 х 10 |
– |
45,8 |
2601 |
|
3 х 25 |
1 х 16 |
– |
45,8 |
2640 |
|
3 х 35 |
1 х 10 |
– |
49,0 |
3132 |
|
3 х 35 |
1 х 16 |
– |
49,0 |
3171 |
|
3 х 50 |
1 х 16 |
– |
52,2 |
3795 |
|
3 х 70 |
1 х 16 |
– |
60,2 |
5077 |
|
3 х 95 |
1 х 25 |
– |
64,1 |
6116 |
|
3 х 120 |
1 х 35 |
– |
67,1 |
7045 |
|
3 х 10 |
1 х 6 |
1 х 6 |
40,4 |
1833 |
|
3 х 16 |
1 х 6 |
1 х 6 |
42,9 |
2175 |
|
3 х 16 |
1 х 10 |
1 х 6 |
42,9 |
2204 |
|
3 х 25 |
1 х 10 |
1 х 6 |
45,7 |
2637 |
|
3 х 35 |
1 х 10 |
1 х 6 |
49,0 |
3169 |
|
3 х 50 |
1 х 16 |
1 х 10 |
52,2 |
3864 |
|
3 х 50 |
1 х 25 |
1 х 10 |
53,7 |
4124 |
|
3 х 70 |
1 х 16 |
1 х 10 |
60,1 |
5139 |
|
3 х 95 |
1 х 25 |
1 х 10 |
64,0 |
6175 |
|
3 х 95 |
1 х 25 |
1 х 16 |
64,0 |
6220 |
|
3 х 120 |
1 х 35 |
1 х 10 |
67,0 |
7104 |
|
Nominal cross-section of main cores, mm² |
Long-term permissible current strength, A |
|
10 |
82 |
|
16 |
106 |
|
25 |
141 |
|
35 |
170 |
|
50 |
213 |
|
70 |
260 |
|
95 |
313 |
|
120 |
367 |
Continuous allowable conductor temperature: not more than 750C.
Maximum operating temperature of conductor: 750C.
Cable winding and unwinding on the drum equals to 10 outer diameters: 7000 cycles.
Cable length: not less 200m.
Ambient temperature: from -300C up to +550C.
Electrical insulation resistance of main conductors at 200C not less than 50 Mom/km
Electrical resistance of conductive shields at temperature 200C not more than 300 Mom.
Nominal alternating voltage frequency 50 Hz:
-main conductors – 6 000V;
-additional conductors – 380V
Alternating test voltage frequency 50Hz, 5 minutes:
-main conductors – 15000V
-additional conductors – 2000V
Cable bending radius:
- Laying and assembly
-not less than 6 outer diameters;
- Winding and unwinding to the drum – not less than 10 outer diameters
Guaranteed operating period: 12 months.
Life period: not less 3 years.