KSHVEmBSHv

1. Main electric conductor – copper multiwire, round or sectoral shape acc. to grade 2 GOST 22483. Additional, ground conductor - copper multiwire, round shape acc. to grade 5 GOST 22483. 

2. Insulation – from PVC compound. Insulation colour of the main conductors – natural, brown, black. Additional conductors have any colouring, except for black and distinct from main conductors colouring. Ground conductor applied without insulation. 

3. Electric conductive shield – from conductive non-woven fabric, winded on main conductor 

4. Metal shield – from copper bands. 

5. Core conductor – shielded, main insulated conductors, additional and ground conductors twisted between each other. Main cable conductors with round shape, inner and outer spaces between conductors filled with harnesses from PVC compound. Main cable conductors with sectoral shape, inner space between conductors filled with harness from PVC compound. 

6. Separating layer – PVC film (for cable with main round shape conductor). 

7. Inner sheath – from PVC compound, laid with filling of inner spaces between conductors to make the cable round shape. 

8. Armour from two steel galvanized bands. 

9. Outer sheath – from PVC compound, coloured in yellow for cable voltage 0,66kV, blue colour for cable voltage 1,2 kV, red colour for cable voltage 6 kV.

For cable KSHVEmBSHvng(A) – inner and outer sheath from low fire performance PVC compound.

For cable KSHVEmBSHvng(A)-LS - inner and outer sheath insulation from low fire hazard PVC compound. 

For cable KSHVEmBSHvng(A)-XL - inner and outer sheath insulation from low fire performance PVC compound with low glass transition temperature. 

To buy products "KSHVEmBSHv" from the manufacturing plant INKATEH LLC and request a price list with the price, call +7 (846) 226-51-73 or fill out an make a request.
Make a request

Mine power cables with copper conductors, insulation and sheath from PVC compound, armoured, KSHVEmBSHv, KSHVEmBSHvng(A), KSHVEmBSHvng(A)-LS, KSHVEmBSHv-XL used for transmission and distribution of electric energy in mine electric networks at horizontal and inclined mine working laying without limitation of level differences on the surfaces of mines, ore mines and wells for suspension to the rope at nominal voltage of main conductors 0,66; 1,2; and 6 kV and nominal alternating voltage of additional conductor 0,38 kV, nominal frequency 50 Hz. 

Maximum network voltage for cable operation – 7,2 kV alternating current. 

Cables must not object to crushing and impact loads. 

Cables should have sealing ends of main conductors. Armouring on the cable ends should be banded. Cable must not be used with damaged outer layer. During cable operation ground conductor should be connected to the ground terminal. 

Displacement of voltage-carrying cables manually strongly prohibited. Transporting of voltagecarrying cables applies with dielectric rubber gloves and footwear or clamp with dielectric handle by operators. Drum must not be laid flatwise as well as cable winding through the drum flange. 

Additional conductor must be connected to the integrity control equipment of ground conductor, which provides alarm and automatic shut-off of the cable line during cable operation. 

It`s necessary to make ground conductor integrity check under operation without additional conductor. Cables must not be used in case of ground and additional conductor malfunction 

Fire hazard grade of cable KSHVEmBSHv, KSHVEmBSHv-XL acc. to GOST 31565: O.1.8.2.5.4 

Fire hazard grade of cable KSHVEmBSHvng(A) acc. to GOST 31565: P.1b.8.2.5.4. 

Fire hazard grade of cable KSHVEmBSHvng(A)-LS acc. to GOST 31565: P.1b.8.2.2.2. 

-Collapse table +Expand table «» Download the table
KSHVEmBSHv
Number and nominal conductor section, mm2 Nominal outer cable diameter, mm Estimated cable weight, kg/km
1,2 kV 6 kV 1,2 kV 6 kV
3х16мк+1х6+1х6 38,9 * 2418
3х25мк+1х10+1х6 34,2 40,2 2290 2793
3х25мк+1х10 * 40,2 * 2792
3х35мк+1х10 * 42,4 * 3243
3х35мк+1х16 36,4 42,4 2697 3292
3х35мк+1х6+1х16 * 42,4 * 3268
3х35мк+1х16+1х6 36,4 42,4 2730 3258
3х35мк+1х16+1х10 * 42,4 * 3311
3х50мк+1х16+1х6 40,7 46 3312 3978
3х50мк+1х16+1х10 * 46 * 4016
3х50мк+1х10+1х16 40,7 46 3475 4023
3х50мк+1х10+3х6 * 46 * 4473
3х50мк+1х10 * 46 * 3873
3х50мк+1х16 * 46 * 3922
3х50мк+1х35 * 46 * 4093
3х70мк+1х16+1х10 * 48,3 * 4675
3х70мк+1х25+1х10 42 48,3 4109 4750
3х95мк+1х16 * 52,3 * 5680
3х95мк+1х25 * 52,3 * 5755
3х95мк+1х10+1х6 * 52,3 * 5669
3х95мк+1х35+1х10 45,9 52,3 5192 6140
3х120мк+1х16 * 55,4 * 6858
3х120мк+1х35+1х10 49 55,4 6162 7044
3х120мк+1х50 * 55,4 * 7150
3х150мк+1х35 * 59,1 * 8117
3х150мк+1х10+1х16 * 59,1 * 7970
3х150мк+1х50+1х10 52,7 59,1 7538 8255
3х185мк+1х50+1х10 57,4 63,1 8590 9658
3х240мк+1х70+1х10 62,6 69,1 11081 11941
3х50мс+1х10 36,6 42,5 2941 3484
3х50мс+1х16 36,6 42,5 2980 3523
3х50мс * 42,5 * 3639
3х70мс+1х10 39,5 45,7 3614 4223
3х70мс+1х16 * 45,7 * 4319
3х70мс+1х25 39,5 45,7 3768 4378
3х95мс+1х10 42,4 48,6 4538 5182
3х95мс+1х16 42,4 48,6 4576 5220
3х95мс+1х25 42,4 48,6 4635 5279
3х95мс+1х35 42,4 48,6 4709 5354
3х120мс * 51,1 * 5895
3х120мс+1х10 * 51,1 * 6027
3х120мс+1х16 45 51,1 5398 6065
3х120мс+1х25 45 51,1 5457 6124
3х120мс+1х35 45 51,1 5531 6198
3х150мс+1х10 * 54,4 * 7298
3х150мс+1х16 48,1 54,4 6406 7336
3х150мс+1х25 48,1 54,4 6465 7395
3х150мс+1х35 48,1 54,4 6539 7470
3х150мс+1х50 48,1 54,4 6635 7565
3х185мс+1х10 * 57,7 * 8505
3х185мс+1х16 51 57,7 7530 8543
3х185мс+1х25 51 57,7 7588 8602
3х185мс+1х35 51 57,7 7663 8676
3х185мс+1х50 51 57,7 7758 8772
3х240мс+1х16 56,1 61,6 9594 10320
3х240мс+1х25 56,1 61,6 9653 10379
3х240мс+1х35 56,1 61,6 9727 10453
3х240мс+1х50 56,1 61,6 9823 10549
3х240мс+1х70 56,1 61,6 9966 10692
To buy products "KSHVEmBSHv" from the manufacturing plant INKATEH LLC and request a price list with the price, call +7 (846) 226-51-73 or fill out an make a request.
Make a request

Type of climatic application acc.to GOST 15150: UXL and XL placement category 1 and 5. 

Cables KSHVEmBSHv and KSHVEmBSHv-XL are flame-retardant at single laying. 

Cables KSHVEmBSHvng(A) and KSHVEmBSHvng(A)-LS are flame-retardant at bunched laying. 

Range of operating cable temperatures KSHVEmBSHv, KSHVEmBSHvng(A), KSHVEmBSHvng(A)-LS: from -50 0C up to +50 0C. 

Range of operating cable temperatures KSHVEmBSHv-XL: from -600C up to +500C. 

Relative atmosphere humidity at temperature up to +350C: up to 98% 

Cable laying and assembly without preheating at temperature not less: -150C. 

Cable conductor continuous heating temperature at work: +700C. 

Maximum allowable temperature of conductors heating at short current circuits: +1600C 

Short circuit duration should not exceed 4 sec. 

Admissible heating of cable conductors in emergency state: not more +900C. 

Operating period of cables in overload period should not exceed 8 hours per day and not more 1000 hours per life period. 

Minimum bending radius at laying not less: 7,5 outer diameters. 

Life period: 5 years, according to stated transportation, storage, laying (assembly) and operation terms. 

Guaranteed operating period: 5 years from the date of putting cable into operation, but not later than 6 months from the production date.