CONSTRUCTION:
1. Electric conductor – copper single or multiwire, round or sectoral shape, according to 1 or 2 grade, GOST 22483.
2. Insulation from halogen-free polymer compound.
3. Core – insulated conductors twisted between each other and fastened by polypropylene thread (for sectoral conductors). Insulated conductors of multiwire cables have distinct colouring. Neutral conductor insulation has blue colouring. Grounding conductor insulation has two-colouring (green-yellow). Inner сore interval from insulated conductors filled with harness, pressed from polyvinylchloride compound. Multiwire cables have equal section conductors. Four conductor cables with section 25 mm2 and more may have one conductor smaller section (neutral or ground conductor).
4. Inner sheath from halogen-free polyvinylchloride compound, laid above with filling of spaces between insulated conductors.
5. Outer sheath – from halogen-free polymer compound.
For shielded cable PPGEng(A)-HF – above inner sheath laid shield from copper bands.
For armouring cable PBPng(A) – above inner sheath laid armouring of two steel galvanized bands.
Flame-retardant power cables with copper conductors, insulation and sheath from halogen-free PVC compound PPGng(A)-HF, PPGEng(A)-HF, PBPng(A)-HF used for transmission and distribution of electric energy in stationary units at nominal alternating voltage 0,66 and 1 kV, nominal frequency up to 100 Hz.
Cables used for wiring in offices with computer and microprocessor hardware, kindergartens, hospitals and for cable lines of entertainment and sport events, as well as supply chain of cable lines and electric control equipment of nuclear power stations (NPS), outside the containment area NPS in systems of grades 3,4 acc. to NP-001-15.
Cables could be used for direct voltage electric networks, not exceeding 2,4U0.
Fire hazard grade acc. to GOST 31565: P16.8.1.2.1.
|
PPGng(A)-HF, PPGEng(A)-HF, PBPng(A)-HF |
||||
|
Number and nominal conductor section, mm² |
Nominal outer cable diameter, mm |
Estimated cable weight, kg/km |
||
|
0,66 kV |
1 kV |
0,66 kV |
1 kV |
|
|
1х6, ок |
6,9 |
7,5 |
100 |
111 |
|
1х10, ок |
8,1 |
8,3 |
150 |
154 |
|
1х16, ок |
9,2 |
9,4 |
214 |
219 |
|
1х25, ок |
10,7 |
10,9 |
314 |
319 |
|
1х35, ок |
11,7 |
11,9 |
408 |
414 |
|
1х50, ок |
13,3 |
13,5 |
543 |
550 |
|
2х6, ок, (N) |
11,8 |
13,0 |
256 |
292 |
|
2х10, ок, (N) |
14,1 |
14,5 |
388 |
403 |
|
2х16, ок, (N) |
17,9 |
18,3 |
628 |
646 |
|
2х25, ок, (N) |
21,0 |
21,4 |
901 |
922 |
|
2х35, ок, (N) |
22,9 |
23,3 |
1143 |
1166 |
|
2х50, ок, (N) |
26,0 |
26,4 |
1501 |
1527 |
|
3х6, ок |
12,4 |
13,7 |
314 |
355 |
|
3х10, ок |
14,9 |
15,4 |
484 |
500 |
|
3х16, ок |
18,9 |
19,3 |
777 |
798 |
|
3х25, ок |
22,1 |
22,5 |
1131 |
1154 |
|
3х35, ок |
24,4 |
24,8 |
1466 |
1492 |
|
3х50, ок |
27,5 |
28,0 |
1920 |
1949 |
|
4х6, ок, (N) |
13,4 |
14,9 |
385 |
433 |
|
4х10, ок, (N) |
16,3 |
16,8 |
599 |
618 |
|
4х16, ок, (N) |
20,5 |
21,0 |
962 |
986 |
|
4х25, ок, (N) |
24,3 |
24,8 |
1421 |
1449 |
|
4х35, ок, (N) |
26,7 |
27,2 |
1845 |
1876 |
|
4х50, ок, (N) |
30,2 |
30,6 |
2421 |
2456 |
|
5х6, ок, (N, PE) |
14,6 |
16,2 |
471 |
528 |
|
5х10, ок, (N, PE) |
17,8 |
18,4 |
740 |
763 |
|
5х16, ок, (N, PE) |
22,3 |
22,8 |
1157 |
1197 |
|
5х25, ок, (N, PE) |
26,5 |
27,1 |
1726 |
1774 |
|
5х35, ок, (N, PE) |
29,2 |
29,7 |
2248 |
2284 |
|
5х50, ок, (N, PE) |
33,5 |
34,4 |
3002 |
3078 |
|
3х25ок+1х16ок, (N) |
24,1 |
24,6 |
1380 |
1374 |
|
3х35ок+1х16ок, (N) |
25,8 |
26,3 |
1691 |
1682 |
|
3х50ок+1х25ок, (N) |
29,2 |
29,6 |
2238 |
2222 |
|
1х16, мк |
9,4 |
9,6 |
225 |
227 |
|
1х25, мк |
11,0 |
11,2 |
331 |
333 |
|
1х35, мк |
12,0 |
12,2 |
426 |
429 |
|
1х50, мк |
14,1 |
14,5 |
587 |
584 |
|
1х70, мк |
* |
15,6 |
* |
766 |
|
1х95, мк |
* |
17,7 |
* |
1033 |
|
1х120, мк |
* |
19,4 |
* |
1282 |
|
1х150, мк |
* |
21,3 |
* |
1586 |
|
1х185, мк |
* |
23,2 |
* |
1969 |
|
1х240, мк |
* |
27,0 |
* |
2584 |
|
1х300, мк |
* |
29,5 |
* |
3193 |
|
2х16, мк, (N) |
18,0 |
18,8 |
651 |
663 |
|
2х25, мк, (N) |
21,2 |
22,0 |
941 |
956 |
|
2х35, мк, (N) |
23,2 |
24,2 |
1223 |
1228 |
|
2х50, мк, (N) |
27,6 |
28,0 |
1656 |
1663 |
|
3х16, мк |
19,0 |
19,8 |
806 |
820 |
|
3х25, мк |
22,4 |
23,2 |
1180 |
1198 |
|
3х35, мк |
25,2 |
25,6 |
1546 |
1553 |
|
3х50, мк |
29,2 |
29,7 |
2102 |
2111 |
|
4х16, мк, (N) |
20,6 |
21,5 |
998 |
1014 |
|
4х25, мк, (N) |
25,1 |
25,6 |
1509 |
1517 |
|
4х35, мк, (N) |
27,5 |
28,0 |
1941 |
1950 |
|
4х50, мк, (N) |
32,5 |
33,0 |
2688 |
2701 |
|
5х16, мк, (N, PE) |
22,5 |
23,4 |
1214 |
1232 |
|
5х25, мк, (N, PE) |
27,4 |
27,9 |
1846 |
1856 |
|
5х35, мк, (N, PE) |
30,1 |
30,6 |
2379 |
2391 |
|
5х50, мк, (N, PE) |
36,0 |
36,6 |
3326 |
3342 |
|
3х50, мс |
* |
26,1 |
* |
1849 |
|
3х70, мс |
* |
29,0 |
* |
2466 |
|
3х95, мс |
* |
33,0 |
* |
3313 |
|
3х120, мс |
* |
35,9 |
* |
4072 |
|
3х150, мс |
* |
39,2 |
* |
5003 |
|
3х185, мс |
* |
43,1 |
* |
6137 |
|
3х240, мс |
* |
48,3 |
* |
7849 |
|
4х50, мс, (N) |
* |
29,3 |
* |
2406 |
|
4х70, мс, (N) |
* |
33,0 |
* |
3268 |
|
4х95, мс, (N) |
* |
37,5 |
* |
4397 |
|
4х120, мс, (N) |
* |
40,5 |
* |
5357 |
|
4х150, мс, (N) |
* |
45,0 |
* |
6695 |
|
4х185, мс, (N) |
* |
49,0 |
* |
8157 |
|
4х240, мс, (N) |
* |
55,3 |
* |
10475 |
|
5х50, мс, (N, PE) |
* |
33,1 |
* |
3055 |
|
5х70, мс, (N, PE) |
* |
37,2 |
* |
4136 |
|
5х95, мс, (N, PE) |
* |
41,9 |
* |
5482 |
|
5х120, мс, (N, PE) |
* |
46,0 |
* |
6772 |
|
5х150, мс, (N, PE) |
* |
50,3 |
* |
8323 |
|
5х185, мс, (N, PE) |
* |
55,5 |
* |
10232 |
|
5х240, мс, (N, PE) |
* |
61,7 |
* |
13002 |
|
3х70мс+1х35ок, (N) |
* |
32,0 |
* |
2902 |
|
3х95мс+1х50мс, (N) |
* |
36,4 |
* |
3931 |
|
3х120мс+1х70мс, (N) |
* |
39,4 |
* |
4856 |
|
3х150мс+1х70мс, (N) |
* |
42,9 |
* |
5839 |
|
3х185мс+1х95мс, (N) |
* |
47,3 |
* |
7237 |
|
3х240мс+1х120мс, (N) |
* |
52,5 |
* |
9160 |
|
2х50, мс, (N) |
* |
22,6 |
* |
1299 |
|
2х70, мс, (N) |
* |
25,0 |
* |
1734 |
|
2х95, мс, (N) |
* |
27,9 |
* |
2310 |
|
2х120, мс, (N) |
* |
29,9 |
* |
2774 |
|
2х150, мс, (N) |
* |
32,6 |
* |
3425 |
|
2х185, мс, (N) |
* |
35,6 |
* |
4189 |
|
2х240, мс, (N) |
* |
39,5 |
* |
5313 |
Type of climatic category acc. to GOST 15150: UXL, placement category 1-5, except laying in ground. Cables are flame-retardant at bunched laying.
Smoke emission at burning and smouldering of cables not decrease light transmission in test chamber more than 40%.
Value of equivalent toxicity index of burning cables not more 40 g/m3 Cables resistant to earthquake intensity up to 9 grades acc.to MSK-64, under neutral mark 60 m.
Cables comply with seismic grade II acc. to NP-031.
Range of operating temperatures: from -50 0C up to +500C.
Relative atmosphere humidity at temperature up to +350C: up to 98% Cable laying and assembly without preheating at temperature not less: -15 0C.
Admissible force at cable tension on the tray should not exceed 50 N/mm2
Cable conductor continuous heating temperature at work: +700C.
Maximum allowable temperature of conductors heating at short current circuits: +1600C Short circuit duration should not exceed 5 sec.
Admissible heating of cable conductors in emergency state: not more +900C.
Operating period of cables in overload period should not exceed 8 hours per day and not more 1000 hours per life period.
Maximum temperature of electric cable conductors without fire outbreak at short circuit – not more 3500C.
Minimum bending radius at laying not less:
- For single wires 10 diameters of cable
- For multiwires 7,5 diameters of cable
Life period: 30 years, according to stated transportation, storage, laying (assembly) and operation terms.
Guaranteed operating period: 5 years from the date of putting cable into operation, but not later 6 months from the production date.