VVGE, VVGEng(A) at 0,66 and 1 kV

Download catalogue
VVGE, VVGEng(A) at 0,66 and 1 kV

CONSTRUCTION: 

1. Electric conductor – copper single or multiwire, round or sectoral shape, according to 1 or 2 grade, GOST 22483. 

2. Insulation from polyvinylchloride compound. Core – insulated conductors twisted between each other and fastened by polypropylene thread (for sectoral conductors). Insulated conductors of multiwire cables have distinct colouring. Neutral conductor insulation has blue colouring. Grounding conductor insulation has two-colouring (green-yellow). Inner сore interval from insulated conductors filled with harness, pressed from polyvinylchloride compound. 

3. Inner sheath from polyvinylchloride compound. 

4. Shield – copper band, laid above inner sheath 

5. Outer sheath from polyvinylchloride compound. 


For cable VVGEng(A) inner and outer sheath from low-flammable polyvinylchloride compound.

To buy products "VVGE, VVGEng(A) at 0,66 and 1 kV" from the manufacturing plant INKATEH LLC and request a price list with the price, call +7 (846) 226-51-73 or fill out an make a request.
Make a request

Power cables with copper conductors, insulation and sheath from polyvinylchloride compound, shielded grades VVGE, VVGEng(A) used for transmission and distribution of electric energy in stationary units at nominal alternating voltage 0,66 and 1 kV, nominal frequency 50 Hz or at direct voltage up to 1 and 1,5 kV. 

Electric networks with ground or insulated neutral in which operating time of single-phase short circuit to ground not exceed 8 hours, overall operating time of singlephase short circuit to ground not exceed 125 hours per year. 

Cables can be laid without limitation of level differences on the routing, including vertical areas. 

Maximum network voltage for operating cables Um equals to 1,2U. 

Cables could be used for direct voltage electric networks, not exceeding 2,4U0. 

Cable grades VVGE used for single cable lines laying in structures and outer (open) electric units (cable tray system, galleries) 

Bunched laying of such cables necessary to use fireproof equipment. 

Cable grades VVGEng(A) used for bunched laying in cable structures and outer (open) electric units (cable tray system, galleries). 

Fire hazard grade for cable VVGE acc.to GOST 31565: O.1.8.2.5.4 

Fire hazard grade for cable VVGEng(A) acc. to GOST 31565: P16.8.2.5.4.

-Collapse table +Expand table Download the table

VVGE, VVGEng(A) 

Number and nominal conductor section, mm²

Nominal outer cable diameter, mm

Estimated cable weight, kg/km

0,66 kV

1 kV

0,66 kV

1 kV

1х6, ок

9,5

10,1

167

182

1х10, ок

10,7

10,9

227

232

1х16, ок

11,6

11,8

294

300

1х25, ок

13,1

13,3

405

411

1х35, ок

14,1

14,3

507

514

1х50, ок

15,5

15,7

646

653

2х6, ок, (N)

14,2

15,4

352

397

2х10, ок, (N)

16,5

16,9

501

518

2х16, ок, (N)

18,3

18,7

669

687

2х25, ок, (N)

21,4

21,8

945

966

2х35, ок, (N)

23,3

23,9

1191

1224

2х50, ок, (N)

26,4

26,8

1550

1576

3х6, ок

14,8

16,1

415

464

3х10, ок

17,3

17,8

602

621

3х16, ок

19,3

19,7

820

840

3х25, ок

22,5

22,9

1177

1200

3х35, ок

24,8

25,2

1515

1540

3х50, ок

27,9

28,4

1970

1998

4х6, ок, (N)

15,8

17,3

493

550

4х10, ок, (N)

18,7

19,2

726

748

4х16, ок, (N)

20,9

21,4

1007

1031

4х25, ок, (N)

24,7

25,2

1469

1497

4х35, ок, (N)

27,1

27,6

1897

1927

4х50, ок, (N)

30,6

31,0

2474

2507

5х6, ок, (N, PE)

17,0

18,6

588

654

5х10, ок, (N, PE)

20,2

20,8

878

903

5х16, ок, (N, PE)

22,7

23,2

1205

1245

5х25, ок, (N, PE)

26,9

27,5

1777

1824

5х35, ок, (N, PE)

29,6

30,1

2303

2338

5х50, ок, (N, PE)

34,3

34,8

3089

3129

3х25ок+1х16ок, (N)

24,5

25,0

1414

1441

3х35ок+1х16ок, (N)

26,2

26,7

1725

1753

3х50ок+1х25ок, (N)

29,6

30,0

2266

2298

1х16, мк

11,8

12,0

300

344

1х25, мк

13,4

13,6

415

467

1х35, мк

14,4

14,6

518

574

1х50, мк

16,3

16,5

682

748

1х70, мк

17,6

942

1х95, мк

20,1

1248

1х120, мк

21,8

1497

1х150, мк

24,1

1821

1х185, мк

26,0

2215

1х240, мк

29,4

2823

1х300, мк

32,3

3465

2х16, мк, (N)

18,4

19,2

688

767

2х25, мк, (N)

21,6

22,4

979

1075

2х35, мк, (N)

23,6

24,6

1238

1345

2х50, мк, (N)

27,8

28,4

1666

1792

3х16, мк

19,4

20,2

840

931

3х25, мк

22,8

23,8

1214

1335

3х35, мк

25,4

26,0

1555

1676

3х50, мк

29,4

30,1

2103

2246

4х16, мк, (N)

21,0

21,9

1046

1133

4х25, мк, (N)

25,3

26,0

1534

1637

4х35, мк, (N)

27,7

28,4

1967

2079

4х50, мк, (N)

32,7

33,4

2741

2841

5х16, мк, (N, PE)

22,9

24,0

1244

1370

5х25, мк, (N, PE)

27,6

28,3

1844

1982

5х35, мк, (N, PE)

30,3

31,0

2375

2527

5х50, мк, (N, PE)

36,2

37,0

3303

3486

3х50, мс

24,8

26,5

1873

1896

3х70, мс

*

29,4

*

2518

3х95, мс

*

33,4

*

3364

3х120, мс

*

35,9

*

4091

3х150, мс

*

39,2

*

5016

3х185, мс

*

43,1

*

6141

3х240, мс

*

48,3

*

7840

4х50, мс, (N)

28,0

30,1

2426

2483

4х70, мс, (N)

*

33,8

*

3352

4х95, мс, (N)

*

38,3

*

4482

4х120, мс, (N)

*

40,5

*

5371

4х150, мс, (N)

*

44,6

*

6653

4х185, мс, (N)

*

49,0

*

8146

4х240, мс, (N)

*

54,9

*

10391

5х50, мс, (N, PE)

31,1

34,0

3056*

3138

5х70, мс, (N, PE)

*

38,1

*

4225

5х95, мс, (N, PE)

*

42,0

*

5493

5х120, мс, (N, PE)

*

45,3

*

6690

5х150, мс, (N, PE)

*

49,9

*

8266

5х185, мс, (N, PE)

*

54,7

*

10097

5х240, мс, (N, PE)

*

61,4

*

12891

3х70мс+1х35ок, (N)

*

32,2

*

2934

3х95мс+1х50мс, (N)

*

36,6

*

3945

3х120мс+1х70мс, (N)

*

39,6

*

4872

3х150мс+1х70мс, (N)

*

43,1

*

5847

3х185мс+1х95мс, (N)

*

47,5

*

7241

3х240мс+1х120мс, (N)

*

53,1

*

9194

2х50, мс, (N)

*

23,0

*

1338

2х70, мс, (N)

*

25,2

*

1762

2х95, мс, (N)

*

28,1

*

2336

2х120, мс, (N)

*

30,1

*

2802

2х150, мс, (N)

*

32,8

*

3447

2х185, мс, (N)

*

35,8

*

4203

2х240, мс, (N)

*

39,7

*

5319

To buy products "VVGE, VVGEng(A) at 0,66 and 1 kV" from the manufacturing plant INKATEH LLC and request a price list with the price, call +7 (846) 226-51-73 or fill out an make a request.
Make a request

Type of climatic category acc. to GOST 15150: UXL, placement category 1-5. 

Cable grades VVGE are flame retardant at single laying. 

Cable grades VVGEng(A) are flame retardant at bunched laying. 

Range of operating temperatures: from -500C up to +500C. 

Relative atmosphere humidity at temperature up to +350C: up to 98% 

Cable laying and assembly without preheating at temperature not less: -150C. 

Admissible force at cable tension on the tray should not exceed 50 N/mm2 

Cable conductor continuous heating temperature at work: +700C. 

Maximum allowable temperature of conductors heating at short current circuits: +1600C 

Short circuit duration should not exceed 5 sec. 

Admissible heating of cable conductors in emergency state: not more +900C. 

Operating period of cables in overload period should not exceed 8 hours per day and not more 1000 hours per life period. 

Maximum temperature of electric cable conductors without fire outbreak at short circuit – not more 3500C. 

Minimum bending radius at laying not less: 

- For single wires 10 diameters of cable 

- For bending wires 7,5 diameters of cable 

Life period: 30 years, according to stated transportation, storage, laying (assembly) and operation terms. 

Guaranteed operating period: 5 years from the date of putting cable into operation, but not later than 6 months from the production date.

To buy products "VVGE, VVGEng(A) at 0,66 and 1 kV" from the manufacturing plant INKATEH LLC and request a price list with the price, call +7 (846) 226-51-73 or fill out an make a request.