CONSTRUCTION:
1. Electric conductor – copper single or multiwire, round or sectoral shape, according to 1 or
2 grade, GOST 22483.
2. Insulation from polyvinylchloride compound. Core – insulated conductors twisted between
each other and fastened by polypropylene thread (for sectoral conductors). Insulated
conductors of multiwire cables have distinct colouring. Neutral conductor insulation has
blue colouring. Grounding conductor insulation has two-colouring (green-yellow). Inner
сore interval from insulated conductors filled with harness, pressed from polyvinylchloride
compound.
3. Inner sheath from polyvinylchloride compound.
4. Outer sheath from polyvinylchloride compound.
For cable grade VVGng(A) inner and outer sheath from low-flammable polyvinylchloride
compound
Power cables with copper conductors, insulation and sheath from polyvinylchloride compound, grade VVG, VVGng(A) used for transmission and distribution of electric energy in stationary units at nominal alternating voltage 0,66 and 1 kV, nominal frequency 50 Hz or at the nominal direct voltage up to 1 and 1,5 kV.
Electric networks with ground or insulated neutral in which operating time of single-phase short circuit to ground not exceed 8 hours, overall operating time of single-phase short circuit to ground not exceed 125 hours per year.
Cables can be laid without limitation of level differences on the routing, including vertical areas.
Maximum network voltage for operating cables Um equals to 1,2U.
Cables could be used for direct voltage electric networks, not exceeding 2,4U0.
VVG cables used for single cable lines laying in structures and outer (open) electric units (cable tray system, galleries) Bunched laying of such cables necessary to use fireproof equipment.
Cable grades VVGng(A) used for bunched laying in cable structures of outer (open) electric units (cable tray system, galleries).
Fire hazard grade for cable grade VVG acc.to GOST 31565: O.1.8.2.5.4
Fire hazard grade for cable grade VVGng(A) acc. to GOST 31565: P16.8.2.5.4.
|
VVG, VVGng(A) |
||||
|
Number and nominal conductor section, mm2 |
Nominal outer cable diameter, mm |
Estimated cable weight, kg/km |
||
|
0,66 kV |
1 kV |
0,66 kV |
1 kV |
|
|
1х6, ок |
6,9 |
7,5 |
96 |
106 |
|
1х10, ок |
8,1 |
8,3 |
145 |
148 |
|
1х16, ок |
9,2 |
9,4 |
208 |
212 |
|
1х25, ок |
10,7 |
10,9 |
305 |
310 |
|
1х35, ок |
11,7 |
11,9 |
398 |
403 |
|
1х50, ок |
13,1 |
13,3 |
524 |
530 |
|
2х6, ок, (N) |
11,8 |
13,0 |
244 |
278 |
|
2х10, ок, (N) |
14,1 |
14,5 |
372 |
385 |
|
2х16, ок, (N) |
17,9 |
18,3 |
575 |
591 |
|
2х25, ок, (N) |
21,0 |
21,4 |
828 |
845 |
|
2х35, ок, (N) |
22,9 |
23,3 |
1056 |
1075 |
|
2х50, ок, (N) |
26,0 |
26,4 |
1389 |
1411 |
|
3х6, ок |
12,4 |
13,7 |
302 |
339 |
|
3х10, ок |
14,9 |
15,4 |
466 |
480 |
|
3х16, ок |
18,9 |
19,3 |
725 |
742 |
|
3х25, ок |
22,1 |
22,5 |
1059 |
1079 |
|
3х35, ок |
24,4 |
24,8 |
1380 |
1402 |
|
3х50, ок |
27,5 |
28,0 |
1810 |
1835 |
|
4х6, ок, (N) |
13,4 |
14,9 |
376 |
421 |
|
4х10, ок, (N) |
16,3 |
16,8 |
586 |
604 |
|
4х16, ок, (N) |
20,5 |
21,0 |
905 |
925 |
|
4х25, ок, (N) |
24,3 |
24,8 |
1341 |
1365 |
|
4х35, ок, (N) |
26,7 |
27,2 |
1751 |
1778 |
|
4х50, ок, (N) |
30,2 |
30,6 |
2301 |
2331 |
|
5х6, ок, (N, PE) |
14,6 |
16,2 |
468 |
524 |
|
5х10, ок, (N, PE) |
17,8 |
18,4 |
739 |
760 |
|
5х16, ок, (N, PE) |
22,3 |
22,8 |
1093 |
1129 |
|
5х25, ок, (N, PE) |
26,5 |
27,1 |
1637 |
1680 |
|
5х35, ок, (N, PE) |
29,2 |
29,7 |
2144 |
2175 |
|
5х50, ок, (N, PE) |
33,5 |
34,4 |
2862 |
2929 |
|
3х25ок+1х16ок, (N) |
24,1 |
24,6 |
1265 |
1288 |
|
3х35ок+1х16ок, (N) |
25,8 |
26,3 |
1562 |
1587 |
|
3х50ок+1х25ок, (N) |
29,2 |
29,6 |
2076 |
2103 |
|
1х16, мк |
7,5 |
10,2 |
225 |
229 |
|
1х25, мк |
8,3 |
11,8 |
329 |
334 |
|
1х35, мк |
9,4 |
12,8 |
423 |
429 |
|
1х50, мк |
10,9 |
14,7 |
574 |
580 |
|
1х70, мк |
15,8 |
761 |
||
|
1х95, мк |
17,9 |
1024 |
||
|
1х120, мк |
19,6 |
1251 |
||
|
1х150, мк |
21,5 |
1529 |
||
|
1х185, мк |
23,4 |
1896 |
||
|
1х240, мк |
27,2 |
2481 |
||
|
1х300, мк |
29,7 |
3058 |
||
|
2х16, мк, (N) |
18,4 |
18,8 |
586 |
490 |
|
2х25, мк, (N) |
21,6 |
22,0 |
851 |
689 |
|
2х35, мк, (N) |
23,6 |
24,4 |
1081 |
874 |
|
2х50, мк, (N) |
27,8 |
28,2 |
1497 |
1172 |
|
3х16, мк |
19,4 |
19,8 |
742 |
760 |
|
3х25, мк |
22,8 |
23,2 |
1091 |
1112 |
|
3х35, мк |
25,4 |
25,8 |
1427 |
1450 |
|
3х50, мк |
29,4 |
29,9 |
1944 |
1970 |
|
4х16, мк, (N) |
21,0 |
21,5 |
925 |
945 |
|
4х25, мк, (N) |
25,3 |
25,8 |
1392 |
1417 |
|
4х35, мк, (N) |
27,7 |
28,2 |
1805 |
1833 |
|
4х50, мк, (N) |
32,7 |
33,2 |
2501 |
2533 |
|
5х16, мк, (N, PE) |
22,9 |
23,4 |
1129 |
1153 |
|
5х25, мк, (N, PE) |
27,6 |
28,1 |
1711 |
1741 |
|
5х35, мк, (N, PE) |
30,3 |
30,8 |
2224 |
2256 |
|
5х50, мк, (N, PE) |
36,2 |
36,8 |
3109 |
3147 |
|
3х50, мс |
24,8 |
25,0 |
1679 |
1697 |
|
3х70, мс |
* |
27,9 |
* |
2296 |
|
3х95, мс |
* |
31,5 |
* |
3073 |
|
3х120, мс |
* |
34,4 |
* |
3808 |
|
3х150, мс |
* |
37,7 |
* |
4708 |
|
3х185, мс |
* |
41,2 |
* |
5756 |
|
3х240, мс |
* |
46,4 |
* |
7401 |
|
4х50, мс, (N) |
28,0 |
28,2 |
2203 |
2227 |
|
4х70, мс, (N) |
* |
31,5 |
* |
3032 |
|
4х95, мс, (N) |
* |
36,0 |
* |
4109 |
|
4х120, мс, (N) |
* |
39,0 |
* |
5043 |
|
4х150, мс, (N) |
* |
42,8 |
* |
6254 |
|
4х185, мс, (N) |
* |
48,0 |
* |
7791 |
|
4х240, мс, (N) |
* |
53,6 |
* |
9932 |
|
5х50, мс, (N, PE) |
31,1 |
31,3 |
2772 |
2786 |
|
5х70, мс, (N, PE) |
* |
35,4 |
* |
3827 |
|
5х95, мс, (N, PE) |
* |
40,1 |
* |
5111 |
|
5х120, мс, (N, PE) |
* |
43,4 |
* |
6275 |
|
5х150, мс, (N, PE) |
* |
48,9 |
* |
7905 |
|
5х185, мс, (N, PE) |
* |
53,4 |
* |
9640 |
|
5х240, мс, (N, PE) |
* |
60,0 |
* |
12366 |
|
3х70мс+1х35ок, (N) |
* |
30,1 |
* |
2674 |
|
3х95мс+1х50мс, (N) |
* |
34,5 |
* |
3651 |
|
3х120мс+1х70мс, (N) |
* |
37,4 |
* |
4550 |
|
3х150мс+1х70мс, (N) |
* |
40,6 |
* |
5458 |
|
3х185мс+1х95мс, (N) |
* |
45,0 |
* |
6794 |
|
3х240мс+1х120мс, (N) |
* |
50,2 |
* |
8738 |
|
2х50, мс, (N) |
* |
21,5 |
* |
1177 |
|
2х70, мс, (N) |
* |
23,5 |
* |
1574 |
|
2х95, мс, (N) |
* |
26,8 |
* |
2145 |
|
2х120, мс, (N) |
* |
28,8 |
* |
2596 |
|
2х150, мс, (N) |
* |
31,1 |
* |
3197 |
|
2х185, мс, (N) |
* |
33,8 |
* |
3895 |
|
2х240, мс, (N) |
* |
38,0 |
* |
5008 |
Type of climatic category acc. to GOST 15150: UXL, placement category 1-5.
VVG cables are flame retardant at single laying.
VVG cables VVGng(A) are flame retardant at bunched laying.
Range of operating temperatures: from -500C up to +500C.
Relative atmosphere humidity at temperature up to +350C: up to 98% Cable laying and assembly without preheating at temperature not less: -150C.
Admissible force at cable tension on the tray should not exceed 50 N/mm2
Cable conductor continuous heating temperature at work: +700C.
Maximum allowable temperature of conductors heating at short current circuits: +1600C
Short circuit duration should not exceed 5 sec.
Admissible heating of cable conductors in emergency state: not more +900C.
Operating period of cables in overload period should not exceed 8 hours per day and not more 1000 hours per life period.
Maximum temperature of electric cable conductors without fire outbreak at short circuit – not more 3500C.
Minimum bending radius at laying not less:
- For single wires 10 diameters cable
- For bending wires 7,5 diameters cable
Life period: 30 years, according to stated transportation, storage, laying (assembly) and operation terms.