VVGng(A)-LS at 0,66 and 1kV

Download catalogue
VVGng(A)-LS at 0,66 and 1kV

CONSTRUCTION: 

1. Electric conductor – copper single or multiwire, round or sectoral shape, according to 1 or 2 grade, GOST 22483. 

2. Insulation from polyvinylchloride compound. Core – insulated conductors twisted between each other. Inner сore interval from insulated conductors filled with harness, pressed from low fire hazard polyvinylchloride compound. Multiwire cables have equal section conductors. Four conductor cables with section 25 mm2 and more may have one conductor smaller section (neutral or ground conductor). 

3. Inner sheath from low fire hazard polyvinylchloride compound, laid with filling spaces between insulated conductors. 

4. Outer sheath from low fire hazard polyvinylchloride compound

To buy products "VVGng(A)-LS at 0,66 and 1kV" from the manufacturing plant INKATEH LLC and request a price list with the price, call +7 (846) 226-51-73 or fill out an make a request.
Make a request

Power cables with copper conductors, insulation and sheath from polyvinylchloride compound, low smoke and gas emissions flame-retardant, grades VVGng(A)-LS used for transmission and distribution of electric energy in stationary units at nominal alternating voltage 0,66 and 1 kV, nominal frequency 50 Hz or at direct voltage up to 1 and 1,5 kV. 

Electric networks with ground or insulated neutral in which operating time of single-phase short circuit to ground not exceed 8 hours, overall operating time of single-phase short circuit to ground not exceed 125 hours per year. Cables can be laid without limitation of level differences on the routing, including vertical areas. 

Maximum network voltage for operating cables Um equals to 1,2U. 

Cables could be used for direct voltage electric networks, not exceeding 2,4U0. 

Cables used for bunched laying including hot loading volume in cable structures and outer (open) electric units in case of mechanical damages and absence of tension force during operating procedures. 

Fire hazard grade acc.to GOST 31565: P1b.8.2.2.2.

-Collapse table +Expand table «»

VVGng(A)-LS

Number and nominal conductor section, mm²

Nominal outer cable diameter, mm

Estimated cable weight, kg/km

0,66 kV

1 kV

0,66 kV

1 kV

1х6, ок

6,9

7,5

105

116

1х10, ок

8,1

8,3

156

160

1х16, ок

9,2

9,4

221

226

1х25, ок

10,7

10,9

323

329

1х35, ок

11,7

11,9

418

425

1х50, ок

13,1

13,3

549

556

2х6, ок, (N)

11,8

13,0

329

397

2х10, ок, (N)

14,1

14,5

485

523

2х16, ок, (N)

15,9

18,3

652

697

2х25, ок, (N)

21,0

21,4

962

991

2х35, ок, (N)

22,9

23,3

1216

1248

2х50, ок, (N)

26,0

26,4

1597

1632

3х6, ок

12,4

13,7

391

464

3х10, ок

14,9

15,4

584

624

3х16, ок

16,9

19,3

806

848

3х25, ок

22,1

22,5

1196

1222

3х35, ок

24,4

24,8

1544

1573

3х50, ок

27,5

28,0

2017

2050

4х6, ок, (N)

13,4

14,9

469

552

4х10, ок, (N)

16,3

16,8

710

753

4х16, ок, (N)

18,5

21,0

995

1042

4х25, ок, (N)

24,3

24,8

1493

1525

4х35, ок, (N)

26,7

27,2

1930

1964

4х50, ок, (N)

30,2

30,6

2527

2566

5х6, ок, (N, PE)

14,6

16,2

565

657

5х10, ок, (N, PE)

17,8

18,4

864

911

5х16, ок, (N, PE)

20,3

22,8

1196

1259

5х25, ок, (N, PE)

26,5

27,1

1806

1858

5х35, ок, (N, PE)

29,2

29,7

2342

2382

5х50, ок, (N, PE)

33,5

34,4

3126

3209

3х25ок+1х16ок, (N)

24,1

24,6

1294

884

3х35ок+1х16ок, (N)

25,8

26,3

1736

1322

3х50ок+1х25ок, (N)

29,2

29,6

2292

2328

1х16, мк

7,5

10,2

241

247

1х25, мк

8,3

11,8

350

356

1х35, мк

9,4

12,8

447

454

1х50, мк

10,9

14,7

604

612

1х70, мк

*

15,8

*

796

1х95, мк

*

17,9

*

1067

1х120, мк

*

19,6

*

1299

1х150, мк

*

21,5

*

1585

1х185, мк

*

23,4

*

1962

1х240, мк

*

27,2

*

2567

1х300, мк

*

29,7

*

3157

2х16, мк, (N)

18,4

18,8

692

619

2х25, мк, (N)

21,6

22,0

998

871

2х35, мк, (N)

23,6

24,4

1256

1096

2х50, мк, (N)

27,8

28,2

1738

1474

3х16, мк

19,4

19,8

847

871

3х25, мк

22,8

23,2

1236

1263

3х35, мк

25,4

25,8

1601

1631

3х50, мк

29,4

29,9

2175

2210

4х16, мк, (N)

21,0

21,5

1040

1086

4х25, мк, (N)

25,3

25,8

1554

1613

4х35, мк, (N)

27,7

28,2

1994

2059

4х50, мк, (N)

32,7

33,2

2753

2883

5х16, мк, (N, PE)

22,9

23,4

1256

1288

5х25, мк, (N, PE)

27,6

28,1

1891

1929

5х35, мк, (N, PE)

30,3

30,8

2434

2475

5х50, мк, (N, PE)

36,2

36,8

3408

3458

3х50, мс

26,9

27,1

1955

1981

3х70, мс

*

30,0

*

2614

3х95, мс

*

34,0

*

3489

3х120, мс

*

36,9

*

4268

3х150, мс

*

40,2

*

5218

3х185, мс

*

44,1

*

6384

3х240, мс

*

49,3

*

8134

4х50, мс, (N)

30,1

30,3

2524

2558

4х70, мс, (N)

*

34,0

*

3445

4х95, мс, (N)

*

38,5

*

4606

4х120, мс, (N)

*

41,5

*

5583

4х150, мс, (N)

*

46,0

*

6960

4х185, мс, (N)

*

50,0

*

8450

4х240, мс, (N)

*

56,3

*

10825

5х50, мс, (N, PE)

33,6

33,8

3177

3203

5х70, мс, (N, PE)

*

37,9

*

4306

5х95, мс, (N, PE)

*

42,6

*

5680

5х120, мс, (N, PE)

*

46,7

*

7001

5х150, мс, (N, PE)

*

50,9

*

8576

5х185, мс, (N, PE)

*

56,1

*

10531

5х240, мс, (N, PE)

*

62,4

*

13342

3х70мс+1х35мс, (N)

*

33,0

*

3153

3х95мс+1х50мс, (N)

*

37,4

*

4242

3х120мс+1х70мс, (N)

*

40,4

*

5198

3х150мс+1х70мс, (N)

*

43,9

*

6237

3х185мс+1х95мс, (N)

*

48,3

*

7705

3х240мс+1х120мс, (N)

*

53,5

*

9707

2х50, мс, (N)

*

23,4

*

1439

2х70, мс, (N)

*

25,8

*

1892

2х95, мс, (N)

*

28,7

*

2500

2х120, мс, (N)

*

30,7

*

2980

2х150, мс, (N)

*

33,6

*

3687

2х185, мс, (N)

*

36,6

*

4493

2х240, мс, (N)

*

40,5

*

5668

To buy products "VVGng(A)-LS at 0,66 and 1kV" from the manufacturing plant INKATEH LLC and request a price list with the price, call +7 (846) 226-51-73 or fill out an make a request.
Make a request

Type of climatic category acc. to GOST 15150: UXL, placement category 1-5. 

Cable grades are flame retardant at bunched laying. 

Smoke emission at burning and smouldering of cables not decrease light transmission in test chamber more than 50%. 

Value of equivalent toxicity index of burning cables not more 40 g/m3 Range of operating temperatures: from -500C up to +500C. 

Relative atmosphere humidity at temperature up to +350C: up to 98% Cable laying and assembly without preheating at temperature not less: -150C. 

Admissible force at cable tension on the tray should not exceed 50 N/mm2 

Cable conductor continuous heating temperature at work: +700C. 

Maximum allowable temperature of conductors heating at short current circuits: +1600C 

Short circuit duration should not exceed 5 sec. 

Admissible heating of cable conductors in emergency state: not more +900C. 

Operating period of cables in overload period should not exceed 8 hours per day and not more 1000 hours per life period. 

Maximum temperature of electric cable conductors without fire outbreak at short circuit – not more 3500C. 

Minimum bending radius at laying not less: 

- For single wires 10 diameters of cable

 - For bending wires 7,5 diameters of cable 


Life period: 30 years, according to stated transportation, storage, laying (assembly) and operation terms. 

Guaranteed operating period: 5 years from the date of putting cable into operation, but not later than 6 months from the production date. 