VBV-XL, VBVng(A)-XL at 6 kV

Download catalogue
VBV-XL, VBVng(A)-XL at 6 kV

CONSTRUCTION: 

1. Electric conductor – copper multiwire, round or sectoral shape,2 grade acc.to GOST 22483. 

2. Insulation from low glass transition temperature PVC compound. Core – three insulated conductors of equal section twisted between each other. Inner сore interval from insulated conductors filled with harness, pressed from polyvinylchloride compound. 

3. Inner sheath (for cables with round conductors) from low glass transition temperature PVC compound laid with filling of spaces between insulated conductors. 

4. Conducting shield as winding from electrically conducting non-woven fabric. 

5. Metal shield from two copper bands. Metal shield nominal section: 16 mm2 for cables with conductor section (16-120) mm2 , 25 mm2 for cables with conductor section (150-240) mm2 

6. Separation layer as winding of polyethylene terephthalate film. 

7. Bedding under armour from low glass transition temperature PVC compound. 

8. Armour protection from two steel galvanized bands. 

9. Outer sheath – from low glass transition temperature PVC compound. 


For cable VBVng(A)-XL inner sheath, bedding under armour and outer sheath from low fire performance PVC compound with low glass transition temperature.

To buy products "VBV-XL, VBVng(A)-XL at 6 kV" from the manufacturing plant INKATEH LLC and request a price list with the price, call +7 (846) 226-51-73 or fill out an make a request.
Make a request

Power cables with copper conductors, insulation and sheath from cold-resistant PVC compound, armoured VBV-XL and VBVng(A)-XL used for transmission and distribution of electric energy in stationary units at nominal voltage 6 kV, nominal frequency 50 Hz. 

Maximum voltage of three-phase network cable -7,2 kV 

Cable VBV-XL designed for single cable line laying in cable structures and buildings. Bunched laying of such cables necessary to use fireproof equipment. 

Cable VBVng(A)-XL used for bunched laying. 

Cables designed for laying in ground (trenches), except for collapsing soils. 

Cables designed for laying in trenches without limitation of level differences. 

Fire hazard grade for cable VBV-XL acc.to GOST 31565: O.1.8.2.5.4 

Fire hazard grade for cable VBVng(A)-XL acc. to GOST 31565: P16.8.2.5.4. 

-Collapse table +Expand table

Cable grade

Number, nominal conductor section and copper shield, mm²

Outer cable diameter, mm

Cable weight, kg/km

VBV-XL, VBVng(A)-XL

3х16мк/16

39

2147

3х25мк/16

41

2577

3х35мк/16

44

2981

3х50мк/16

47

3627

3х50мс/16

41

2988

3х70мс/16

44

3686

3х95мс/16

47

4564

3х120мс/16

50

5355

3х150мс/25

54

6738

3х185мс/25

57

7868

3х240мс/25

61

9548

To buy products "VBV-XL, VBVng(A)-XL at 6 kV" from the manufacturing plant INKATEH LLC and request a price list with the price, call +7 (846) 226-51-73 or fill out an make a request.
Make a request

Type of climatic category acc. to GOST 15150: XL, placement category 1 and 5. 

Cables VBV-XL are flame-retardant at single laying. 

Cables VBVng(A)-XL are flame-retardant at bunched laying. Range of operating temperatures: from -600C up to +500C. 

Relative atmosphere humidity at temperature up to +350C: up to 98% Cable laying and assembly without preheating at temperature not less: -250C. 

Admissible force at cable tension on the tray should not exceed 50 N/mm2 Cable conductor continuous heating temperature at work: +700C. 

Maximum allowable temperature of conductors heating at short current circuits: +1600C Short circuit duration should not exceed 5 sec. 

Admissible heating of cable conductors in emergency state: not more +800C. 

Operating period of cables in overload period should not exceed 8 hours per day and not more 1000 hours per life period. 

Maximum temperature of electric cable conductors without fire outbreak at short circuit – not more 3500C. 

Minimum bending radius at laying not less: 7,5 outer diameters. 

Life period: 30 years, according to stated transportation, storage, laying (assembly) and operation terms. 

Guaranteed operating period: 5 years from the date of putting cable into operation, but not later than 6 months from the production date.

To buy products "VBV-XL, VBVng(A)-XL at 6 kV" from the manufacturing plant INKATEH LLC and request a price list with the price, call +7 (846) 226-51-73 or fill out an make a request.
Make a request

Request call back
* — required fields